Medium and high voltage power cables

Common information


Area of application:

Area of application: N2XSY, NA2XSY, N2XSY-LS, NA2XSY-LS, N2XS2Y, NA2XS2Y, N2XS2Y, NA2XS2Y, N2XS(F)2Y, NA2XS(F)2Y, N2XS(FL)2Y, NA2XS(FL)2Y, N2XS(FL)2Y, NA2XS(FL)2Y type power cables are used during stationary installation specified for distribution and transmission of electric power. Cables are used in areas without external mechanical effects, renches and underground.

N2XS(F)2Y, NA2XS(F)2Y, N2XS(FL)2Y, NA2XS(FL)2Y type cables are used under high humidity grounds, constantly humid and flooded right-of-ways with complex configuration.

N2XSSEB2Y, NA2XSSEB2Y type cables are used in right-of-ways with complicated configuration, since they are protected from external mechanical effects.

Technical parameters:
  • Rated operation voltage: 6, 10, 20, 35, 64/110 kV – single core.
  • Rated operation voltage: 6, 10, 20, 35kV – triple core
  • Core lateral section mm2: 50 ÷ 1200(single core); 50 ÷240 (triple core)
  • Relative humidity: 98% at 35°C temperature
  • Nisbi rütubətlilik: 35°C-də 98%
  • Core heating temperature during short circuit: 250°C
  • Shield heating temperature during short circuit: 350°C
  • Service life: 30 years



N2XS2Y 10 kV

Cable type Nominal cross-section area, mm Minimum lateral section of copper shielding, mm2 Wire design weight, kg/km Electrical resistance of 1km long wire
N2XS2Y 10 kV 1 x 50 16 915,5 0,387
1 x 70 1129,1 0,268
1 x 95 1388,5 0,193
1 x 120 1615,6 0,153
1 x 150 25 2026,2 0,124
1 x 185 2361,3 0,0991
1 x 240 2864,3 0,0754
1 x 300 3470,8 0,0601
1 x 400 35 4493,8 0,0470
1 x 500 5428,2 0,0336

NA2XS2Y 20 kV

Cable type Nominal cross-section area, mm Minimum lateral section of copper shielding, mm2 Wire design weight, kg/km Electrical resistance of 1km long wire
NA2XS2Y 20 kV 1 x 50 16 762,0 0,641
1 x 70 863,4 0,443
1 x 95 976,6 0,320
1 x 120 1075,7 0,253
1 x 150 25 1290,8 0,206
1 x 185 1429,2 0,164
1 x 240 1629,3 0,125
1 x 300 1858,6 0,100
1 x 400 35 2304,2 0,0778
1 x 500 2673,8 0,0605

N2XSY 64/110 kV

Cable type Nominal cross-section area, mm Minimum lateral section of copper shielding, mm2 Wire design weight, kg/km Electrical resistance of 1km long wire
N2XSY 64/110 kV 1 x 185 35 4682,9 0,0991
1 x 240 5291,3 0,0754
1 x 300 6056,8 0,0601
1 x 400 7016,1 0,0470
1 x 500 8146,1 0,0336
1 x 630 9536,8 0,0283
1 x 800 11412,9 0,0211

N2XS2Y 35 kV

Cable type Nominal cross-section area, mm Minimum lateral section of copper shielding, mm2 Wire design weight, kg/km Electrical resistance of 1km long wire
N2XS2Y 35 kV 1 x 50 16 1345,8 0,387
1 x 70 1585,3 0,268
1 x 95 1875,7 0,193
1 x 120 2124,2 0,153
1 x 150 25 2561,6 0,124
1 x 185 2922,5 0,0991
1 x 240 3483,5 0,0754
1 x 300 4123,0 0,0601
1 x 400 35 5193,7 0,0470
1 x 500 6172,1 0,0336

NA2XS2Y 10 kV

Cable type Nominal cross-section area, mm Minimum lateral section of copper shielding, mm2 Wire design weight, kg/km Electrical resistance of 1km long wire
NA2XS2Y 10 kV 1 x 50 16 614,7 0,641
1 x 70 706,3 0,443
1 x 95 810,1 0,320
1 x 120 901 0,253
1 x 150 25 1107,1 0,206
1 x 185 1235,5 0,164
1 x 240 1422,8 0,125
1 x 300 1639,9 0,100
1 x 400 35 2066,4 0,0778
1 x 500 2394,1 0,0605

NA2XS2Y 64/110 kV

Cable type Nominal cross-section area, mm Minimum lateral section of copper shielding, mm2 Wire design weight, kg/km Electrical resistance of 1km long wire
NA2XS2Y 64/110 kV 1 x 185 35 3557,1 0,164
1 x 240 3849,7 0,125
1 x 300 4225,9 0,100
1 x 400 4588,8 0,0778
1 x 500 5112,0 0,0605
1 x 630 5696,8 0,0469
1 x 800 6502,2 0,0367

N2XS2Y 20 kV

Cable type Nominal cross-section area, mm Minimum lateral section of copper shielding, mm2 Wire design weight, kg/km Electrical resistance of 1km long wire
N2XS2Y 20 kV 1 x 50 16 1062,7 0,387
1 x 70 1286,2 0,268
1 x 95 1555 0,193
1 x 120 1790,303 0,153
1 x 150 25 2209,9 0,124
1 x 185 2554,9 0,0991
1 x 240 3070,8 0,0754
1 x 300 3689,5 0,0601
1 x 400 35 4731,5 0,0470
1 x 500 5707,8 0,0336

NA2XS2Y 35 kV

Cable type Nominal cross-section area, mm Minimum lateral section of copper shielding, mm2 Wire design weight, kg/km Electrical resistance of 1km long wire
NA2XS2Y 35 kV 1 x 50 16 1045,1 0,641
1 x 70 1162,5 0,443
1 x 95 1297,4 0,320
1 x 120 1409,6 0,253
1 x 150 25 1642,5 0,206
1 x 185 1796,7 0,164
1 x 240 2041,9 0,125
1 x 300 2292,1 0,100
1 x 400 35 2766,3 0,0778
1 x 500 3138,1 0,0605

Сonstruction: N2XS2Y, N2XSY, N2XS2Y, N2XS(F)2Y, N2XS(F)2Y, N2XS(FL)2Y

  • 1. Copper or aluminum wire current carrying core
  • 2. Extruded semi-conductive shield conductor.
  • 3. XLPE Insulation.
  • 4. Extruded semi-conductive shield insulation.
  • 5. Copper wire shield
  • 6. FIller for voids between cores
  • 7. Polyethylene sheath (or PVC).

Сonstruction: N2XSEBY, N2XSEB2Y, N2XSE(F)B2Y

  • 1. Copper or aluminum wire current carrying core
  • 2. Extruded semi-conductive shield conductor.
  • 3. XLPE Insulation
  • 4. Extruded semi-conductive shield insulation.
  • 5. Copper wire shield
  • 6. FIller for voids between cores
  • 7. Double galvanized steel tape armor
  • 8. Polyethylene sheath (or PVC).