Medium and high voltage power cables
Common information
Area of application: N2XSY, NA2XSY, N2XSY-LS, NA2XSY-LS, N2XS2Y, NA2XS2Y, N2XS2Y, NA2XS2Y, N2XS(F)2Y, NA2XS(F)2Y, N2XS(FL)2Y, NA2XS(FL)2Y, N2XS(FL)2Y, NA2XS(FL)2Y type power cables are used during stationary installation specified for distribution and transmission of electric power. Cables are used in areas without external mechanical effects, renches and underground.
N2XS(F)2Y, NA2XS(F)2Y, N2XS(FL)2Y, NA2XS(FL)2Y type cables are used under high humidity grounds, constantly humid and flooded right-of-ways with complex configuration.
N2XSSEB2Y, NA2XSSEB2Y type cables are used in right-of-ways with complicated configuration, since they are protected from external mechanical effects.
- Rated operation voltage: 6, 10, 20, 35, 64/110 kV – single core.
- Rated operation voltage: 6, 10, 20, 35kV – triple core
- Core lateral section mm2: 50 ÷ 1200(single core); 50 ÷240 (triple core)
- Relative humidity: 98% at 35°C temperature
- Nisbi rütubətlilik: 35°C-də 98%
- Core heating temperature during short circuit: 250°C
- Shield heating temperature during short circuit: 350°C
- Service life: 30 years
N2XS2Y 10 kV
Cable type | Nominal cross-section area, mm | Minimum lateral section of copper shielding, mm2 | Wire design weight, kg/km | Electrical resistance of 1km long wire |
---|---|---|---|---|
N2XS2Y 10 kV | 1 x 50 | 16 | 915,5 | 0,387 |
1 x 70 | 1129,1 | 0,268 | ||
1 x 95 | 1388,5 | 0,193 | ||
1 x 120 | 1615,6 | 0,153 | ||
1 x 150 | 25 | 2026,2 | 0,124 | |
1 x 185 | 2361,3 | 0,0991 | ||
1 x 240 | 2864,3 | 0,0754 | ||
1 x 300 | 3470,8 | 0,0601 | ||
1 x 400 | 35 | 4493,8 | 0,0470 | |
1 x 500 | 5428,2 | 0,0336 |
NA2XS2Y 20 kV
Cable type | Nominal cross-section area, mm | Minimum lateral section of copper shielding, mm2 | Wire design weight, kg/km | Electrical resistance of 1km long wire |
---|---|---|---|---|
NA2XS2Y 20 kV | 1 x 50 | 16 | 762,0 | 0,641 |
1 x 70 | 863,4 | 0,443 | ||
1 x 95 | 976,6 | 0,320 | ||
1 x 120 | 1075,7 | 0,253 | ||
1 x 150 | 25 | 1290,8 | 0,206 | |
1 x 185 | 1429,2 | 0,164 | ||
1 x 240 | 1629,3 | 0,125 | ||
1 x 300 | 1858,6 | 0,100 | ||
1 x 400 | 35 | 2304,2 | 0,0778 | |
1 x 500 | 2673,8 | 0,0605 |
N2XSY 64/110 kV
Cable type | Nominal cross-section area, mm | Minimum lateral section of copper shielding, mm2 | Wire design weight, kg/km | Electrical resistance of 1km long wire |
---|---|---|---|---|
N2XSY 64/110 kV | 1 x 185 | 35 | 4682,9 | 0,0991 |
1 x 240 | 5291,3 | 0,0754 | ||
1 x 300 | 6056,8 | 0,0601 | ||
1 x 400 | 7016,1 | 0,0470 | ||
1 x 500 | 8146,1 | 0,0336 | ||
1 x 630 | 9536,8 | 0,0283 | ||
1 x 800 | 11412,9 | 0,0211 |
N2XS2Y 35 kV
Cable type | Nominal cross-section area, mm | Minimum lateral section of copper shielding, mm2 | Wire design weight, kg/km | Electrical resistance of 1km long wire |
---|---|---|---|---|
N2XS2Y 35 kV | 1 x 50 | 16 | 1345,8 | 0,387 |
1 x 70 | 1585,3 | 0,268 | ||
1 x 95 | 1875,7 | 0,193 | ||
1 x 120 | 2124,2 | 0,153 | ||
1 x 150 | 25 | 2561,6 | 0,124 | |
1 x 185 | 2922,5 | 0,0991 | ||
1 x 240 | 3483,5 | 0,0754 | ||
1 x 300 | 4123,0 | 0,0601 | ||
1 x 400 | 35 | 5193,7 | 0,0470 | |
1 x 500 | 6172,1 | 0,0336 |
NA2XS2Y 10 kV
Cable type | Nominal cross-section area, mm | Minimum lateral section of copper shielding, mm2 | Wire design weight, kg/km | Electrical resistance of 1km long wire |
---|---|---|---|---|
NA2XS2Y 10 kV | 1 x 50 | 16 | 614,7 | 0,641 |
1 x 70 | 706,3 | 0,443 | ||
1 x 95 | 810,1 | 0,320 | ||
1 x 120 | 901 | 0,253 | ||
1 x 150 | 25 | 1107,1 | 0,206 | |
1 x 185 | 1235,5 | 0,164 | ||
1 x 240 | 1422,8 | 0,125 | ||
1 x 300 | 1639,9 | 0,100 | ||
1 x 400 | 35 | 2066,4 | 0,0778 | |
1 x 500 | 2394,1 | 0,0605 |
NA2XS2Y 64/110 kV
Cable type | Nominal cross-section area, mm | Minimum lateral section of copper shielding, mm2 | Wire design weight, kg/km | Electrical resistance of 1km long wire |
---|---|---|---|---|
NA2XS2Y 64/110 kV | 1 x 185 | 35 | 3557,1 | 0,164 |
1 x 240 | 3849,7 | 0,125 | ||
1 x 300 | 4225,9 | 0,100 | ||
1 x 400 | 4588,8 | 0,0778 | ||
1 x 500 | 5112,0 | 0,0605 | ||
1 x 630 | 5696,8 | 0,0469 | ||
1 x 800 | 6502,2 | 0,0367 |
N2XS2Y 20 kV
Cable type | Nominal cross-section area, mm | Minimum lateral section of copper shielding, mm2 | Wire design weight, kg/km | Electrical resistance of 1km long wire |
---|---|---|---|---|
N2XS2Y 20 kV | 1 x 50 | 16 | 1062,7 | 0,387 |
1 x 70 | 1286,2 | 0,268 | ||
1 x 95 | 1555 | 0,193 | ||
1 x 120 | 1790,303 | 0,153 | ||
1 x 150 | 25 | 2209,9 | 0,124 | |
1 x 185 | 2554,9 | 0,0991 | ||
1 x 240 | 3070,8 | 0,0754 | ||
1 x 300 | 3689,5 | 0,0601 | ||
1 x 400 | 35 | 4731,5 | 0,0470 | |
1 x 500 | 5707,8 | 0,0336 |
NA2XS2Y 35 kV
Cable type | Nominal cross-section area, mm | Minimum lateral section of copper shielding, mm2 | Wire design weight, kg/km | Electrical resistance of 1km long wire |
---|---|---|---|---|
NA2XS2Y 35 kV | 1 x 50 | 16 | 1045,1 | 0,641 |
1 x 70 | 1162,5 | 0,443 | ||
1 x 95 | 1297,4 | 0,320 | ||
1 x 120 | 1409,6 | 0,253 | ||
1 x 150 | 25 | 1642,5 | 0,206 | |
1 x 185 | 1796,7 | 0,164 | ||
1 x 240 | 2041,9 | 0,125 | ||
1 x 300 | 2292,1 | 0,100 | ||
1 x 400 | 35 | 2766,3 | 0,0778 | |
1 x 500 | 3138,1 | 0,0605 |
Сonstruction: N2XS2Y, N2XSY, N2XS2Y, N2XS(F)2Y, N2XS(F)2Y, N2XS(FL)2Y
- 1. Copper or aluminum wire current carrying core
- 2. Extruded semi-conductive shield conductor.
- 3. XLPE Insulation.
- 4. Extruded semi-conductive shield insulation.
- 5. Copper wire shield
- 6. FIller for voids between cores
- 7. Polyethylene sheath (or PVC).
Сonstruction: N2XSEBY, N2XSEB2Y, N2XSE(F)B2Y
- 1. Copper or aluminum wire current carrying core
- 2. Extruded semi-conductive shield conductor.
- 3. XLPE Insulation
- 4. Extruded semi-conductive shield insulation.
- 5. Copper wire shield
- 6. FIller for voids between cores
- 7. Double galvanized steel tape armor
- 8. Polyethylene sheath (or PVC).